PSR-SCP-230UC/ESAM4/3X1/1X2/B
-
Safety relays
2901428
Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e in accordance with EN ISO 13849, 2-channel operation, 3 enabling current paths, nominal input voltage: 230 V AC/DC, plug-in screw terminal blocks
Free download available.
Downloads
Product details
| Note on application | |
| Note on application | Only for industrial use |
| Product type | Safety relays |
| Product family | PSRclassic |
| Application | Emergency stop |
| Safety door | |
| Control | 2-channel |
| Mechanical service life | approx. 107 cycles |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Insulation characteristics | |
| Overvoltage category | II, III (See the section “Insulation coordination”) |
| Degree of pollution | 2 |
| Times | |
| Typical response time | 300 ms (automatic start) |
| 40 ms (manual, monitored start) | |
| Typ. starting time with Us | 330 ms (when controlled via A1) |
| Typical release time | 20 ms (when controlled via S11/S12 and S21/S22) |
| 150 ms (when controlled via A1) | |
| Recovery time | 1 s |
| Maximum power dissipation for nominal condition | 16.4 W (At IL² = 72 A²,PTotal max = 2 W + 14.4 W) |
| Nominal operating mode | 100% operating factor |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage/insulation | 4 kV / basic insulation (safe isolation, reinforced insulation, and 6 kV between A1-A2/logic/enabling and signaling current paths) |
| Supply | |
| Designation | A1/A2 |
| Rated control circuit supply voltage US | 230 V AC -15 % / +10 % |
| Rated control supply current IS | typ. 22 mA (at UN) |
| Apparent power | typ. 4.5 VA (at UN) |
| Protective circuit | Surge protection |
| Varistor | |
| Digital: Sensor circuit (S12, S22) | |
| Description of the input | safety-related |
| Concurrence | ∞ |
| Max. permissible overall conductor resistance | 50 Ω |
| Protective circuit | Surge protection |
| Suppressor diode | |
| Digital: Start circuit (S34) | |
| Description of the input | non-safety-related |
| Concurrence | ∞ |
| Max. permissible overall conductor resistance | 50 Ω |
| Protective circuit | Surge protection |
| Suppressor diode | |
| Relay: Enabling current paths (13/14, 23/24, 33/34) | |
| Number of outputs | 3 (undelayed) |
| Contact switching type | 3 enabling current paths |
| Contact material | AgSnO2, + 0.2 µm Au |
| Switching voltage | min. 10 V AC/DC |
| max. 250 V AC/DC | |
| Switching power | min. 100 mW |
| Inrush current | min. 10 mA |
| max. 6 A | |
| Switching capacity | 6 A (24 V (DC13)) |
| 5 A (230 V (AC15)) | |
| Limiting continuous current | 6 A (observe derating) |
| Sq. Total current | 72 A2 (observe derating) |
| Switching frequency | max. 0.5 Hz |
| Mechanical service life | 10x 106 cycles |
| Interrupting rating (ohmic load) max. | see load limit curve |
| Output fuse | 10 A gL/gG NEOZED |
| Relay: Signaling current path (41/42) | |
| Number of outputs | 1 (undelayed) |
| Contact switching type | 1 signaling current path |
| Contact material | AgSnO2, + 0.2 µm Au |
| Switching voltage | min. 10 V AC/DC |
| max. 250 V AC/DC | |
| Switching power | min. 100 mW |
| Inrush current | min. 10 mA |
| max. 6 A | |
| Limiting continuous current | 5 A |
| Sq. Total current | 72 A2 (observe derating) |
| Switching frequency | max. 0.5 Hz |
| Output fuse | 6 A gL/gG NEOZED |
| Connection technology | |
| pluggable | yes |
| Conductor connection | |
| Connection method | Screw connection |
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section AWG | 24 ... 12 |
| Status display | 3 x LED (green) |
| Operating voltage display | 1 x LED (green) |
| Width | 22.5 mm |
| Height | 99 mm |
| Depth | 114.5 mm |
| Color | yellow (RAL 1018) |
| Housing material | PA |
| Safety data | |
| Stop category (EN 60204-1) | 0 |
| Safety data: EN ISO 13849 | |
| Performance level (PL) | e (5 A DC13; 8760 switching cycles/year) |
| Safety data: IEC 61508 - High demand | |
| Safety Integrity Level (SIL) | 3 |
| Safety data: IEC 61508 - Low demand | |
| Safety Integrity Level (SIL) | 3 |
| Safety data: EN IEC 62061 | |
| Safety Integrity Level (SIL) | 3 |
| Ambient conditions | |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Shock | 15g |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| Conformity/Approvals | |
| Conformance | CE-compliant |
| Mounting type | DIN rail mounting |
| Mounting position | any |
| Item number | 2901428 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Product key | DNA114 |
| GTIN | 4046356592062 |
| Weight per piece (including packing) | 199.51 g |
| Weight per piece (excluding packing) | 177.09 g |
| Customs tariff number | 85371098 |
| Country of origin | DE |
ECLASS
| ECLASS-13.0 | 27371819 |
| ECLASS-15.0 | 27371819 |
| ECLASS-15.0 ASSET | 27250101 |
ETIM
| ETIM 10.0 | EC001449 |
UNSPSC
| UNSPSC 21.0 | 39122200 |
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes |
| Exemption | 7(a), 7(c)-I |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-50
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
| SCIP | 573d5547-f8c2-4c90-b439-dabfe824bf4e |
| EF3.1 Climate Change | |
| CO2e kg | 6.063 kg CO2e |
Compatible products
Your advantages
Up to Cat. 4/PL e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
Manually monitored and automatic activation in a single device
Basic insulation
1- and 2-channel control
3 enabling current paths, 1 signaling current path
Phoenix Contact GmbH & Co. KG
Flachsmarktstraße 8, D-32825 Blomberg