MINI-DC-UPS/24DC/2
-
Uninterruptible power supply
2866640
Uninterruptible power supply with integrated power supply unit, 2 A, in combination with MINI-BAT/24/DC 0.8 AH or 1.3 AH
This product needs further products for operation.
Mandatory accessories
Product details
| DC operation | |
| Input voltage range | 100 V DC ... 350 V DC |
| Voltage type of supply voltage | DC |
| Inrush current | < 34 A (< 1.1 A2s) |
| Inrush current integral (I2t) | < 1.1 A2s |
| Mains buffering time | see diagram |
| Buffer period | 20 min (2 A) |
| Rotary selector switch | Can be set to: 0.5 min; 1 min; 2 min; 3 min; 5 min; 10 min; 15 min; 20 min; 30 min; permanent |
| Current consumption | 0.6 A |
| 0.85 A (230 V AC) | |
| 1.1 A | |
| 1.5 A (120 V AC) | |
| Protective circuit | Varistor |
| Power factor (cos phi) | approx. 0.5 |
| Typical response time | 100 ms |
| Input fuse | 3.15 A (slow-blow, internal) |
| Permissible backup fuse | B6 B10 B16 |
| Recommended breaker for input protection | 6 A ... 16 A (Characteristics B, C, D, K) |
| AC operation | |
| Nominal input voltage range | 100 V AC ... 240 V AC |
| Input voltage range | 85 V AC ... 264 V AC |
| Voltage type of supply voltage | AC |
| Efficiency | > 83 % |
| Nominal output voltage | 24 V DC (AC input voltage available: 22.5 to 29.5 V DC, AC input voltage not available: 27.9 to 19.2 V DC) |
| Setting range of the output voltage (USet) | 22.5 V DC ... 29.5 V DC (normal mode; in the buffer mode, dependent on a battery voltage of 27.9 V DC ... 19.2 V DC) |
| Nominal output current (IN) | 2 A |
| Output current limit | max. 3 A |
| Bridging time | 1200 s |
| Derating | 60 °C ... 70 °C (2.5 %/K) |
| Feedback voltage resistance | 35 V DC |
| Protection against overvoltage at the output (OVP) | < 35 V DC |
| Max. capacitive load | unlimited |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
| Residual ripple | < 50 mVPP |
| Output power | 48 W |
| Peak switching voltages nominal load | < 100 mVPP |
| Maximum no-load power dissipation | 3.8 W |
| Power loss nominal load max. | 15 W |
| Power dissipation battery operation | 2.1 W |
| Rise time | < 100 ms |
| Connection in parallel | yes |
| Connection in series | no |
| Mains operation | |
| Nominal output voltage | 24 V DC |
| Output voltage range | 22.5 V DC ... 29.5 V DC |
| Nominal output current (IN) | 2 A |
| Battery operation | |
| Nominal output voltage | 24 V DC |
| Output voltage range | 19.2 V DC ... 27.6 V DC (UOUT = UBAT - 0,5 V DC) |
| Nominal output current (IN) | 2 A |
| Signal: Active (high = buffer module is loaded) | |
| Output description | Power Good |
| Maximum switching voltage | ≤ 24 V |
| Output voltage | + 24 V |
| Continuous load current | ≤ 20 mA |
| Signal: Alarm | |
| Output description | Relay output |
| Maximum switching voltage | ≤ 24 V |
| Output voltage | 24 V |
| Continuous load current | ≤ 200 mA |
| Signal: Battery charge | |
| Output description | Relay output |
| Maximum switching voltage | ≤ 24 V |
| Output voltage | 24 V |
| Continuous load current | ≤ 200 mA |
| Signal: Battery mode | |
| Output description | Relay output |
| Maximum switching voltage | ≤ 24 V |
| Output voltage | 24 V |
| Continuous load current | ≤ 200 mA |
| Charging current | 1 A |
| Nominal capacity range | 0.8 Ah ... 1.3 Ah |
| Memory medium | external, battery 0.8 Ah / 1.3 Ah |
| IQ technology | no |
| Network management | No |
| Input | |
| Connection method | Pluggable COMBICON screw connections |
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Conductor cross-section AWG min. | 24 |
| Conductor cross-section AWG max. | 12 |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Output | |
| Connection method | Pluggable COMBICON screw connections |
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Conductor cross-section AWG min. | 24 |
| Conductor cross-section AWG max. | 12 |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Signal | |
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Conductor cross-section AWG min. | 24 |
| Conductor cross-section AWG max. | 12 |
| Screw thread | M3 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Types of signaling | LED |
| Signal output: Active (high = buffer module is loaded) | |
| Status display | LED "Power Good", green |
| Note on status display | Buffer module is loaded: LED ON |
| Signal output: Alarm | |
| Status display | LED (red) |
| Note on status display | Malfunction/alarm: LED permanently lit |
| Signal output: Battery charge | |
| Status display | LED flashing yellow |
| Note on status display | Battery charge/battery is being charged: LED flashing |
| Signal output: Battery mode | |
| Status display | LED (yellow) |
| Note on status display | Battery mode/buffer mode: LED permanently lit |
| Insulation voltage input/output | 4 kV (type test) |
| 2 kV (routine test) |
| Product family | MINI UPS – UPS with integrated power supply |
| IQ technology | no |
| MTBF (IEC 61709, SN 29500) | > 753000 h (40 °C) |
| Insulation characteristics | |
| Protection class | II (in closed control cabinet) |
| Degree of pollution | 2 |
| Width | 67.5 mm |
| Height | 99 mm |
| Depth | 107 mm |
| Installation dimensions | |
| Installation distance right/left | 0 mm / 0 mm |
| Installation distance top/bottom | 30 mm / 30 mm |
| Mounting type | DIN rail mounting |
| Assembly note | alignable: horizontally 0 mm, vertically 50 mm |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Housing material | Plastic |
| Type of housing | Polyamide PA, color: green |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Max. permissible relative humidity (operation) | 95 % (at 25 °C, non-condensing) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g, 90 min. | |
| Rail applications | EN 50121-4 |
| Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
| Standard - Electrical safety | EN 60950-1/VDE 0805 (SELV) |
| EN 61558-2-17 | |
| Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | EN 50178 |
| Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
| EN 60204 (PELV) | |
| Standard - Safe isolation | DIN VDE 0100-410 |
| UL approvals | UL Listed UL 508 |
| UL/C-UL Recognized UL 60950-1 | |
| UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| EMC requirements for noise emission | EN 61000-6-3 |
| EN 61000-6-4 | |
| EMC requirements for noise immunity | EN 61000-6-1 |
| EN 61000-6-2 | |
| Noise emission | |
| Standards/regulations | EN 55011 (EN 55022) |
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 |
| Housing | Level 3 |
| Electrostatic discharge | |
| Contact discharge | 6 kV |
| Discharge in air | 8 kV |
| Comments | Criterion B |
| Electromagnetic HF field | |
| Standards/regulations | EN 61000-4-3 |
| Electromagnetic HF field | |
| Frequency range | 80 MHz ... 2 GHz |
| Test field strength | 10 V/m |
| Comments | Criterion A |
| Fast transients (burst) | |
| Standards/regulations | EN 61000-4-4 |
| Fast transients (burst) | |
| Input | 4 kV (level 4 - asymmetrical: conductor to ground) |
| Output | 2 kV (level 3 - asymmetrical: conductor to ground) |
| Signal | 1 kV (level 2 - asymmetrical: conductor to ground) |
| Comments | Criterion B |
| Surge voltage load (surge) | |
| Standards/regulations | EN 61000-4-5 |
| Surge voltage load (surge) | |
| Input | 4 kV (level 4 - asymmetrical: conductor to ground) |
| 2 kV (level 4 - symmetrical: conductor to conductor) | |
| Output | 2 kV (Level 3 - asymmetrical) |
| 1 kV (Level 3 - symmetrical) | |
| Signal | 2 kV (Level 3 - asymmetrical) |
| 1 kV (Level 3 - symmetrical) | |
| Comments | Criterion B |
| Conducted interference | |
| Standards/regulations | EN 61000-4-6 |
| Conducted interference | |
| Input/output/signal | Level 3 |
| Frequency range | 10 kHz ... 80 MHz |
| Comments | Criterion A |
| Voltage | 10 V |
| Voltage dips | |
| Standards/regulations | EN 61000-4-11 |
| Emitted interference | |
| Standards/regulations | EN 61000-6-3 |
| Radio interference voltage in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
| Item number | 2866640 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Product key | CMUM13 |
| GTIN | 4046356113533 |
| Weight per piece (including packing) | 496 g |
| Weight per piece (excluding packing) | 447 g |
| Customs tariff number | 85371091 |
| Country of origin | CN |
ECLASS
| ECLASS-13.0 | 27040705 |
| ECLASS-15.0 | 27040705 |
ETIM
| ETIM 9.0 | EC000382 |
UNSPSC
| UNSPSC 21.0 | 39121000 |
| EU RoHS | |
| Fulfills EU RoHS substance requirements | Yes |
| Exemption | 7(a), 7(c)-I |
| China RoHS | |
| Environment friendly use period (EFUP) |
EFUP-25
An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required.
|
| EU REACH SVHC | |
| REACH candidate substance (CAS No.) | Lead (CAS: 7439-92-1) |
| SCIP | 2b4b9094-1235-45d0-bf72-fefce9e27e6c |
| EF3.1 Climate Change | |
| CO2e kg | 9.642 kg CO2e |
Compatible products
Your advantages
High operational safety - comprehensive signaling and temperature-dependent battery charging
Fast installation – minimal wiring effort with COMBICON connectors for easy connection
Phoenix Contact GmbH & Co. KG
Flachsmarktstraße 8, D-32825 Blomberg